串聯電抗器的作用
在輸配電系統中存在許多諧波源,如大功率的晶閘管整流和調節裝置、電弧爐等,若直接投入并聯電容器,由于回路參數的改變往往會導致系統諧波分量的放大,嚴重的還會產生諧振。高壓并聯電容器組通常接入一定電抗率的串聯電抗器抑制電容器接入電網而引起的諧波放大。
電容器的合閘涌流
電(dian)容(rong)(rong)(rong)器(qi)(qi)的(de)(de)兩端電(dian)壓不能突變,在(zai)(zai)電(dian)容(rong)(rong)(rong)器(qi)(qi)投入(ru)電(dian)網的(de)(de)瞬間,電(dian)容(rong)(rong)(rong)器(qi)(qi)相當于短(duan)路(lu),特別在(zai)(zai)將(jiang)電(dian)容(rong)(rong)(rong)器(qi)(qi)投入(ru)在(zai)(zai)運行中的(de)(de)電(dian)容(rong)(rong)(rong)器(qi)(qi)組(zu)并聯時,會(hui)產生高頻率(lv)和高幅值的(de)(de)暫態過(guo)電(dian)流,稱為(wei)涌流。涌流的(de)(de)大小與電(dian)容(rong)(rong)(rong)器(qi)(qi)組(zu)接(jie)入(ru)處(chu)母線的(de)(de)短(duan)路(lu)容(rong)(rong)(rong)量有關系(xi)。
合閘涌流的限制要求
通過電感的電流不能突變的原理,將電容器組與電抗器串聯,就能有效的限制電容器組投入電網時產生的涌流。
在電(dian)(dian)容(rong)(rong)器(qi)組接入接入處的(de)(de)母線短路容(rong)(rong)量(liang)不超過(guo)電(dian)(dian)容(rong)(rong)器(qi)容(rong)(rong)量(liang)的(de)(de)50倍時,單(dan)個電(dian)(dian)容(rong)(rong)器(qi)組的(de)(de)合閘涌流不超過(guo)電(dian)(dian)容(rong)(rong)器(qi)額定(ding)電(dian)(dian)流的(de)(de)10倍。 高頻和(he)高幅值的(de)(de)涌流對于電(dian)(dian)容(rong)(rong)器(qi)、開關設(she)(she)備的(de)(de)觸頭和(he)回(hui)路其他設(she)(she)備將造成破壞。根據國內多年(nian)的(de)(de)運行經驗,發現電(dian)(dian)容(rong)(rong)器(qi)裝置的(de)(de)合閘涌流在20倍的(de)(de)電(dian)(dian)容(rong)(rong)器(qi)額定(ding)電(dian)(dian)流情況(kuang)下,未(wei)見對回(hui)路設(she)(she)備造成損(sun)壞,所以涌流的(de)(de)限制(zhi)宜取(qu)20倍,當超過(guo)時應予限制(zhi)。
串聯電抗器在實際使用中分類
一是主要用于限制電力諧波放大的串聯電抗器。這類串聯電抗器的接入可以有效的抑制某次電力諧波在系統中的放大。如5%的串抗可以抑制5次及以上的諧波,12%的串抗可以抑制3次及以上諧波。這類電抗器均有比較高電感值,可以有效抑制涌流峰值及頻率。