某(mou)鋼廠由(you)一路10kV電(dian)(dian)源進線,廠內安(an)裝兩(liang)臺(tai)中(zhong)頻爐變壓(ya)(ya)器(qi),單臺(tai)容量(liang)為(wei)(wei)3150kVA,變壓(ya)(ya)等(deng)(deng)級為(wei)(wei)10kV/720V。中(zhong)頻爐在投入運(yun)行時產生了大量(liang)的諧波(bo)電(dian)(dian)流,由(you)測量(liang)結果可知(zhi),變壓(ya)(ya)器(qi)的自(zi)然(ran)功率因數為(wei)(wei)0.72,電(dian)(dian)壓(ya)(ya)總畸變率最大為(wei)(wei)9.0%,其諧波(bo)電(dian)(dian)流組成主要為(wei)(wei)5、7、11等(deng)(deng)次諧波(bo)電(dian)(dian)流,超過國家規定。
(1)由于無功補償裝置在設(she)計(ji)時并未考慮到裝置運行的(de)(de)諧波環(huan)境,使得所(suo)設(she)計(ji)的(de)(de)裝置結構參數不適(shi)應其(qi)所(suo)處的(de)(de)環(huan)境,造(zao)成諧波電(dian)(dian)流的(de)(de)嚴重放大,大大超過(guo)其(qi)運行的(de)(de)額定電(dian)(dian)流,從而造(zao)成電(dian)(dian)容器(qi)之路元(yuan)件燒壞、跳閘現象的(de)(de)發生(sheng),嚴重威脅(xie)電(dian)(dian)容器(qi)單元(yuan)的(de)(de)正(zheng)常安全運行。
(2)比較(jiao)10KV母線(xian)的實測數據和相(xiang)關的系統參數,中(zhong)頻(pin)電(dian)(dian)爐投入運(yun)(yun)行時的諧波電(dian)(dian)流全(quan)部注入電(dian)(dian)網,其數值(zhi)大大超過國(guo)標所(suo)限定的允(yun)許值(zhi),嚴重污(wu)染電(dian)(dian)網,威脅電(dian)(dian)網設備的安全(quan)運(yun)(yun)行,也(ye)影響同一條目線(xian)上其他用(yong)電(dian)(dian)企(qi)業的用(yong)電(dian)(dian)設備的正常運(yun)(yun)行。
為限制中頻電爐投入運行時產生的諧波電流大量注入電網,需安裝專用濾波補償裝置。這樣不但解決了諧波電(dian)流的嚴(yan)重放(fang)大(da)問題,降(jiang)低對電(dian)網的諧波污染(ran),改善(shan)公司其他用電(dian)設備的運行環境,而且功率因數也能滿足供電(dian)部門和(he)企業要求。
濾波(bo)補償裝置采(cai)用雙反相并聯晶(jing)閘管,實(shi)現過(guo)零投切,無(wu)沖(chong)擊(ji)、無(wu)涌流和過(guo)電(dian)壓,不產生暫態和諧波(bo)。無(wu)觸(chu)點(dian)開關可實(shi)現電(dian)容(rong)器的連續快速投切。